DjFanCoilController
v2 v3 13 13 ||1.22 || ||14/09/2020 ||christo.malan ||Fix fan speed sdo, use fan % and not step[[BR]]fix 1s timeout for inputs, move code to interrupt[[BR]]fix demo temp not updated in pdo[[BR]]Always update fan speed in Mulitzone mode[[BR]]fix fan rundown, reload as long as mode is not off fix fan max|| 14 14 ||1.23 || ||29/09/2020 ||christo.malan ||Add, Calculate EC fan speed from diffusers[[BR]]if temperature is < 0.5C, no sensor, switch off heater[[BR]]fix use fanspeed for Aux and OCC mode[[BR]]add fallback mode for noDiffusers and noMaster[[BR]]remove compiler warnings[[BR]]detect that an other device is polling and reset[[BR]]Fix, only set noDiffuer if Multi Zone is enabled|| 15 ||1.24|| ||13/10/2020||christo.malan||**Recaled** Fix network startup timing. \\Prevent unoccupied mode from switching the unit on.|| 16 ||1.25|| ||02/11/2020||christo.malan||Fix overflow in diffuser control fan speed \\Fix min fan speed for PI output of 0% \\Load PI settings during upgrade set to defaults and if 0.|| 17 ||1.26|| ||06/11/2020||christo.malan||Remove "fix network startup timing" added in V1.24. Fixed in wallstat version 4.19.||