Issue: 4 ||= Version =||= MinHW =||= Date =||= Done by =||= Reason =|| ||1.00 || ||2018/07/18 ||gavin.mutch || First Major Release || ||1.01 || ||2018/08/01 ||gavin.mutch || Fixed change-over heating/cooling bug || ||1.02 || ||2018/08/02 ||gavin.mutch || Added support for setpoint/sense temperature sharing between Fan Coils via Loop Number || ||1.04 || ||02/08/2018 ||gavin.mutch || Found the previous bug was not fully fixed. Fixed an issue where OFF had highest priority, but showed up as overriden when an input was triggered. || ||1.05 || ||07/08/2018 ||gavin.mutch || Included SDO 48 (Occupancy override) for Christo. || ||1.06 || ||29/11/2018 ||christo.malan || Fix loop jumping || ||1.07 || ||09/02/2019 ||christo.malan || Add rundown timer, keep fan on if heater was on. Fix Manual Fan and Auto valve mode. || ||1.20 || ||18/06/2020 ||christo.malan ||Major Update:[[BR]]Fix heater, only switch on after the hot valve opened [[BR]]Add diffuser control: use ave diffuser temp and sp,fan control based on ave disk [[BR]]Add new valve modes 2-10V and 6 way valve [[BR]] Use change over for both valves.|| ||1.21 || ||21/08/2020 ||christo.malan ||fix valve change over operation [[BR]] Keep heater off if not in use [[BR]]Implement heater minimum Off time (if switched off keep it off for minimum of 15s)|| ||1.22 || ||14/09/2020 ||christo.malan ||Fix fan speed sdo, use fan % and not step[[BR]]fix 1s timeout for inputs, move code to interrupt[[BR]]fix demo temp not updated in pdo[[BR]]Always update fan speed in Mulitzone mode[[BR]]fix fan rundown, reload as long as mode is not off fix fan max|| ||1.23 || ||29/09/2020 ||christo.malan ||Add, Calculate EC fan speed from diffusers[[BR]]if temperature is < 0.5C, no sensor, switch off heater[[BR]]fix use fanspeed for Aux and OCC mode[[BR]]add fallback mode for noDiffusers and noMaster[[BR]]remove compiler warnings[[BR]]detect that an other device is polling and reset[[BR]]fix, only set noDiffuer if diffuser controll is on||