Version 6 (modified by 2 years ago) (diff) | ,
---|
Version | MinHW | Date | Done by | Reason |
---|---|---|---|---|
6.00 | 4 | 2011/11/22 | mvdeventer | New version 4 hardware |
6.03 | 4 | 2012/12/05 | mvdeventer | Updates for Lighting Control with wired light switch Only do I2C comms (occupancy and flow) when the slave comms is idle |
6.04 | 4 | 2013/13/01 | mvdeventer | In chip Command Added again Fix I2C comms sync Add flow sensor functions |
6.05 | 4 | 2013/26/02 | mvdeventer | Improve I2C occupancy comms Enable WDT, was off for debug Rework Flow averaging calculation LightSwitchChipIn - send occupancy status PDO immediately Add overide indication Remove Stratification mode again |
6.06 | 4 | 2013/26/02 | mvdeventer | Add sdo to read occupancy sensor identification info |
6.07 | 4 | 2013/26/02 | mvdeventer | Disable motor before reboot, to ensure that all motor off during a software update |
6.08 | 4 | 2013/05/22 | mvdeventer | Update bootloader to disable motor, to ensure that the motor is not drawing current in boot loader mode Rework the watchdog timer |
6.09 | 4 | 2013/05/22 | mvdeventer | Recalled control did not work change occ sensitivity from 6 to 8 |
6.10 | 4 | 2014/02/24 | mvdeventer | Fix 6.09 Add intelligent (I2C) heater functionality, ensure the heater minimum on value is 10% Add SDO 35 36 37 for flow control from MCU |
6.11 | 4 | 2014/03/30 | mvdeventer | Add heater control bits, Control / Status heater control bits Restore WDT |
6.12 | 4 | 2014/06/06 | mvdeventer | Add Occupancy enable/disable(present) and Occupancy detected Add Flow detected(sensor connected) |
6.13 | 4 | 2014/06/06 | mvdeventer | Fix flow if no occupancy sensor is connected |
6.14 | 4 | 2015/01/19 | mvdeventer | Correcty handle 0Pa reading from flow sensor Don't do Control Override on Zone 0 |
6.15 | 4 | 2016/09/28 | christo.malan | Add heater control and other change over modes DM0073-0014 |
6.16 | 4 | 2017/11/13 | mvdeventer | Added valve control for 24VAC Valves |
6.17 | 4 | 2019/07/25 | christo.malan | Stagger motor initialisation, prevent motors from hitting the endstop all at the same time (prevent power supply problems) |
6.18 | 4 | 2019/11/19 | christo.malan | Add flow offset SDO |
6.19 | 4 | 2020/02/17 | mvdeventer | Stability improvements for I2C code (Flow and Occupancy) Rolling average on Flow/pressure value Add software reset command for flow sensor error recovery |
6.20 | 4 | 2020/04/02 | christo.malan | Remove flow updates from 6.19 Disable button if pressed at startup. Add sdo to show if it is disabled |
6.21 | 4 | 2020/06/22 | christo.malan | Add flow updates from 6.19 |
6.22 | 4 | 2020/07/24 | christo.malan | Clear flow connected flag if no sensor is connected Add pressure test sdo 65 |
6.23 | 4 | 2021/03/18 | christo.malan | Add network lock(not used) Remove OCC chip in Save button disable state in flash |
6.24 | 4 | 2021/04/09 | christo.malan | Network Lock release DM0073-0015 |
6.25 | 4 | 2021/07/07 | christo.malan | Add setting to report change over mode with a negative disk position. sdo 66 Make the changeover dead band a setting. sdo 66 Mirror disk position at changeover |
6.26 | 4 | 2021/10/28 | christo.malan | Fix occupancy trigger (Not working since V6.23) Remove - Mirror disk position at changeover added in V6.25 Hot start release DM0073-0018 |
6.27 | 4 | 2022/09/05 | christo.malan | Add led indication for broken comms packets |