Table of Contents
- 06.01K
- 06.02K
- 06.03K
- 06.04K
- 06.05K
- 06.06K
- 06.07K
- 06.08K
- 06.09K
- 06.10K
- 06.11K
- 06.12K
- 06.13K
- 06.14K
- 06.15K
- 06.16K
- 06.17M
- 06.18K
- 06.19K
- 06.20K
- 06.21K
- 06.22K
- 06.23K
- 06.24K
- 06.25K
- 06.26K
- 06.27K
- 06.28K
- 06.29K
- 06.30K
- 06.31K
- 06.32K
- 06.33K
- 06.34K
- 06.35K
- 06.36K
- 06.37K
- 06.38K
- 06.45K
- 06.46K
- 06.47K
- 06.48K
- 06.50K
- 06.51K/M
- 06.52K/M
- 06.53K/M
- 05.01B
- 05.02B
- 05.03B
- 05.04T
- 05.04M
- 05.05B
- 05.06B
- 05.07B
- 05.07T
- 05.09B
- 05.??
- 05.11B
- 05.12M
- 05.13M
- 05.14B
- 05.14T
- 05.14M
- 05.15B
- 05.16B
- 05.17B
V6
06.01K
2013/09/13
- Add bacnet activation key
06.02K
2014/02/25
- Add min flow control code
06.03K
2014/03/31
- Fix version and size header of flow constants
06.04K
2014/04/17
- Fix bug version and size header of flow constants
06.05K
2014/05/14
- Add flow max pi loop
- Add pi settings to flow coff file
- Improve write speed
06.06K
2014/06/25
- Fix feedback for max flow control
- Prevent overflow for Pa < 0
- Only mark pdos as outdated for write sdos
06.07K
2014/08/20
- Add global occ override
- Add global control override
- Disable CLKOUT (80MHz) prevent EMI
06.08K
2015/02/11
- Add usb connectivity:
- Use MLM app with only the usb cable connected
- Use usb cable to show and change IP and other settings
- Update code to work with new ftp bootloader
- Check if config and flow coff files are valid before using it
06.09K
2015/03/06
- Add option to change bacnet port.
- Remove flow debug prints.
06.10K
2016/03/02
- Change broadcast to subnet and not 255.255.255.255
- Limit flow PI loop between motor min and max
06.11K
2016/05/24
- Change frontend code format
- New frontend code to fix flash update and MM2 send delays
- speed up node flash updates
- Implement CO write and fix temp write
- fix broken webpages
06.12K
2016/06/21
- Add pcd setpoint
- remove deg F for now
06.13K
2016/06/28
- Fix flow setpoint 25.5 bug
06.14K
2016/07/08
- add deg F setpoint again
- Prevent flow from going < 0
- Change AO_RELINQUISH_DEFAULT based on unit type
06.15K
2016/08/19
- Fix PCD setpoint 25.5 bug for good
06.16K
2016/10/06
- Fix negative presure for PCD
- Add altitude correction to flow calculation
06.17M
2017/10/03
- Add set_name to change mcu name with terminal
06.18K
2017/05/03
- Add CO2 value and SP
06.19K
2017/07/12
- Add CO2 flow
06.20K
2017/11/01
- Version to upgrade bootloader
06.21K
2017/11/02
- Fix Host Id for RF
- Fix Motor Min and Max to write to zone not just the master
- Add multi state input for RF status
06.22K
2018/05/29
- Add AV point for CO2 and remove sharing with room temp (added in 6.18K)
06.23K
2018/09/05
- Fan Coil
- Add BACnet data points
- Allow mode change (off,fan,on)
- Remove CO2 setpoint (added in 6.18K)
- Add key with serial and mac to query string (Fix DM0073-0006)
- Add diffuser(host) type(D,P,F), serial no and name separated with a colon: to description on all bacnet points
- Fix MSI for PCD mode
06.24K
2018/09/17
- Fix BACnet write for room temperature, was broken since 6.21K
06.25K
2019/02/10
- Update Fancoil mode, set mode on wallsat if connected
- Report negative value for control disk, Diffuser CO mode indication
06.26K
2019/08/15
- Add option to reverse occ override modes as per (wrong)documentation
06.27K
2019/11/19
- Add flow offset
- Update IP settings webpage to validate new IP automatically.
06.28K
2020/04/03
- Test Version disable disk and setpoint writes for PCD's
06.29K
2020/04/19
- Allow writes to AV points to be disabled.
- Add BMS cmd for PCD's
06.30K
2020/04/23
- Update wording on BACnet webpage
- Clear zone table for channel, when the channel data is cleared
06.31K
2020/04/06
- Not released
06.32K
2020/04/06
- Webpage layout/format updates
- Show live data on bacnet page
- Use external ram for node flash updates, allow for bigger node code(now works with AP and new WS code)
06.33K
2020/06/24
- Make flash update compatible with older MLM Tool. Use flash file unless data is send over upd.
- Some more webpage improvements.
06.34K
2020/07/23
- Update front end code to prevent never ending master stop
- Validate mlm config file entries while loading, and abort if an entry is invalid.
- Delete the config file if file size is smaller than header size.
- Delete flow coff file if file size and entry count don't match.
06.35K
2020/08/27
- Calculate network quality every 255 polls
- Reboot on name change from webpage.
06.36K
2020/11/09
- New frontend code to fix FCU id resolve reset loop. FCU V1.24 and V1.25.
06.37K
2020/11/10
- Remove FCU fix from 6.36
- Fix MSO updates - updates from the MLM tool did not reflect in the priory array
06.38K
2020/12/15
- Skip 0C temps for global bacnet ave temp
06.45K
2021/01/22
- First iPSU version
06.46K
2021/07/07
- Add flow limits to BACnet AI property 8000(flow min) and 8001(flow max)
- Add diffuser name to web page display
- Get zone CO2 from wallstat that have a CO2 sensor
06.47K
2022/04/07
- Add BACnet CO2/RHT Setpoint at AO 120 - 180, CO2 Low setpoint is high minus 200 ppm RHT Low setpoint is high minus 10%
- If RHT is active, replace CO2 with RHT on AV point
06.48K
2022/04/12
- Fix RH/CO2 value and update css on BACnet webpage.
06.50K
- Prevent temperature setpoint overflow for sp < 14
06.51K/M
2022/07/14
- Fix Fancoil mode MSO
06.52K/M
2022/08/19
- Fix Fancoil mode value on webpage
- Make fan speed writable (Need FC wallstat version 8.11 or later)
- Rename Fancoil operating Mode state text to be the same as MLM Tool
- Ignore BACnet setpoint write of 0 degC
06.53K/M
2022/09/09
- Fix Fancoil fan speed uint on webpage
- Fix Fan speed set, if a fancoil zone is without a wallstat.
V5
05.01B
2012/09/07
First release
05.02B
2012/09/09
Fix default bacnet id
Pulse led on button press
Add external ram test
Fix file system size for flash update
05.03B
2012/09/11
Fix reset message
05.04T
2012/10/18
Release Plain version
05.04M
2012/10/19
MS/TP relase
05.05B
2012/11/06
Add disk avg
Add deg C/F flags
copy defaluts to end of parameter when new parameters is added
05.06B
2013/02/01
Fix zone table udp read and write
Add Global setpoint
Add avg room temp
05.07B
2013/03/06
Change front end buffer strategy to prevent channel lockup (sync route and flash update)
Add code to detect a blocked channel and reset all front ends
05.07T
2013/03/06
Create plain version
05.09B
2013/04/19
Wait less time for master stop.
Send master start when sync fail
Add flow code - not called
Send routed pdo on every poll
05.??
reset msp before flash update start
reset msp on data timeout
mark sdo for read at pdo data
clear data only for the polled channel don't loop all ch on every poll
add 2min reset for no data
clear ram only after 3 min
route every pdo 10 times
05.11B
2013/05/30
fix idle diffuser at routing
fix possible bug bms cmd write form bacnet
add some debug print flags
fix empty route table not writing to flash
05.12M
2013/06/20
remove more debug messages
fix mstp buffered data not being sent after 5ms
fix mstp requests for packets longer as 255 bytes
extend qspi startup to 15ms after frontend reset
extend routed message repeat to 15 polls
export bacnet datalink settings in makefile
05.13M
2013/06/27
fix mstp response buffer lockup
change time for flahupdate start
change fash update upd response
some changes to debug frontend bootloader
update make file for bip
05.14B
2013/09/11
New bootloader V002.002
-fix USB id strings
-lock flash
refactor mlm state machine
change qspi to use ringbuffer.c
add bootloader for msp frontends
change TCP buffer to use 4 windows to improve performance
fix how router task read the message buffer
update makefile to auto calculate dependencies
build now include the correct webpages in the app
reset zone table on loop save
05.14T
2013/09/11
Plain version
05.14M
2013/09/11
MS/TP version
05.15B
2014/02/26
add occ override
try to fix sync start delay
05.16B
2014/06/03
add global occ override
add global control override
add poll and delay between sdos
remove unnecessary master stop commands
05.17B
2014/07/18
Make writes faster