Changes between Version 4 and Version 5 of DjFanCoilController


Ignore:
Timestamp:
04/16/21 16:14:17 (4 years ago)
Author:
Christo
Comment:

--

Legend:

Unmodified
Added
Removed
Modified
  • DjFanCoilController

    v4 v5  
    99||1.06 || ||29/11/2018 ||christo.malan || Fix loop jumping ||
    1010||1.07 || ||09/02/2019 ||christo.malan || Add rundown timer, keep fan on if heater was on. Fix Manual Fan and Auto valve mode. ||
    11 ||1.20 || ||18/06/2020 ||christo.malan || **Major Update:** Minimum Wallstat Version is **8.08 **[[BR]]Fix heater, only switch on after the hot valve opened [[BR]]**Add Multi Zone control:** use ave diffuser temp and sp,fan control based on ave disk. Minimum diffuser wallstat version is 4.19[[BR]]Add new valve modes 2-10V and 6 way valve [[BR]] Use change over for both valves. ||
     11||1.20 || ||18/06/2020 ||christo.malan || **Major Update:** Minimum Wallstat Version is **8.08 ** \\Add new valve modes 2-10V and 6 way valve \\Use change over for both valves. Fix heater, only switch on after the hot valve opened. \\**Add Multi Zone control:** Use average diffuser temperature and setpoint and control fan speed based on average diffuser disk. Minimum diffuser wallstat version is 4.19 for Multi Zone||
    1212||1.21 || ||21/08/2020 ||christo.malan || fix valve change over operation [[BR]]  Keep heater off if not in use [[BR]]Implement heater minimum Off time (if switched off keep it off for minimum of 15s) ||
    1313||1.22 || ||14/09/2020 ||christo.malan || Fix fan speed sdo, use fan % and not step[[BR]]fix 1s timeout for inputs, move code to interrupt[[BR]]fix demo temp not updated in pdo[[BR]]Always update fan speed in Mulitzone mode[[BR]]fix fan rundown, reload as long as mode is not off fix fan max ||